Descripción

Function Insulation monitor
System type AC
Nominal voltage to 500 V
Reponse value type Einstellbar
Reponse value kOhm ... kOhm 5 - 100 Ohm
Enclosure design Installationsverteiler
Width 70 mm
Type IP 5880
According to IEC/EN 61 557-8 For single and 3-phase AC-systems up to 0 ... 500 V and 10 ... 10000 Hz Adjustable tripping value RAL of 5 ... 100 k&Omega, Monitors also disconnected voltage systems De-energized on trip Auxiliary voltage Measuring Circuit and output contacts are galvanically separated Manual and auto reset With test and reset button Connections of external test and reset buttons possible LED indicators for operation and alarm 2 changeover contacts IL/SL 5880/200 with additional prewarning- adjustable prewarning value 10 k&Omega, ... 5 M&Omega,- output function programmable Variant IL/SL 5880/300 according to DIN VDE 0100-551 for mobile generator sets available 4 models available:IL 5880, IP 5880: 61 mm deep with terminals near to the bottom to be mounted in consumer unitsor industrial distribution systems according to DIN 43 880SL 5880, SP 5880: 98 mm deep with terminals near to the top to be mounted in cabinets withmounting plate and cable ducts DIN rail or screw mounting 35 mm width''